VFD · Drives
WEEK OF APR 28
Delta VFD-8 · EngineeredAir DJ-40-C

The VFD that wasn't actually broken.

Overcurrent trips, repeated restarts — the obvious call was a drive replacement. HVAC Hero surfaced wrong motor parameters instead. Drive saved.

Saved · ~$400 part
Liam Howden · Naylor
Boiler · Hydronic
WEEK OF MAR 24
Laars 20L 100A-GCL

Two boilers. Two faults. One bad board.

The results pointed one way. The logic pointed another. HVAC Hero walked the swap table and found one bad board — not two.

Saved · 1 extra part avoided
Luke Beamish · Naylor
Heat pump · Reversing valve
WEEK OF MAY 12
Tempstar PHD46000K000F1 · R-410A

The reversing valve that froze the coil.

New evaporator, low suction, intermittent coil freeze in cooling. The tech was eyeing the filter drier — HVAC Hero caught a 20°F drop across the reversing valve body and pinned the restriction inside the valve.

Saved · Wrong part avoided
James Toller · Brian Cox
Rooftop · Controls
WEEK OF MAY 18
Carrier 48FCDM07 · SystemVu

The contactor that wasn't the problem.

Blower running, compressor dead, no SystemVu access. HVAC Hero walked Y1-C → J3B → contactor coil and proved the MBB output was failing — not the contactor.

Saved · Right board condemned
Calob Cleveland · Enteck Solutions
Rooftop · Network
WEEK OF MAY 1
Lennox LGA048H2BH3G · Prodigy 2.0

Code 93 keeps coming back.

AC kicking on during heat calls. The tech was about to swap a 3-phase monitor and an ignition control — HVAC Hero ruled both out, ID'd a lost network sensor, and walked Nathan into the Network Integration menu.

Saved · 2 wrong parts avoided
Nathan Burroughs · All Hours HVAC
Packaged heat pump · Sensors
WEEK OF MAY 1
York XN060 · Smart Equipment Control

The sensor that was never there.

Board posting CC2 sensor fail. HVAC Hero verified the CC1 reading (13kΩ at 65°F vs. expected 13.4kΩ), then surfaced that CC2 was never landed at install. Open input, not a failed sensor.

Saved · No part ordered
Leo Kivell · Frey Lutz